Bykski
4U Rackmount Server Liquid Cooling Unit for 8-GPU Loops | Bykski B-640TK100-SPD-X
4U cooling distribution unit for GPU servers
The Bykski B-640TK100-SPD-X is a 4U rackmount cooling distribution unit for custom liquid cooling loops in 8-GPU servers. Its built-in pump circulates coolant through the server loop, and a 100 mm copper radiator with six fans releases heat to the air. The front SPD touchscreen lets you monitor the loop and adjust pump and fan speeds.
Rack & Loop Fit
Plan for a 4U mounting position and a server liquid cooling loop.
- ✓4U rack space with room for the 452.5 mm deep chassis, rear hose bends, and airflow
- ✓An 8-GPU server loop with water blocks selected for the individual cards
Before ordering, check the available mounting depth and confirm each water block fits the exact GPU model and PCB.
Design Highlights
Five-layer copper radiator
The 100 mm thick radiator uses five layers of coolant channels and high-density W-shaped fins. The core is constructed using high-temperature welding.
Integrated pump and reservoir
The pump sits beneath a reservoir that holds about 900 mL. A front window lets you check the coolant level directly. Use the SPD touchscreen to view loop readings and set alert thresholds.
Six radiator fans
The radiator is paired with six industrial dual-ball-bearing fans with thickened, high-strength PVC blades. The SPD controller lets you adjust fan speed from the front panel.
Key Specifications
| Model | B-640TK100-SPD-X |
|---|---|
| Chassis format | 4U rackmount |
| Chassis (D × W × H) | 452.5 × 440 × 175 mm |
| Weight | 27.5 kg |
| Frame material | Aluminum alloy |
| Color | Black |
| Radiator material | All copper |
| Radiator thickness | 100 mm |
| Radiator channels | Five layers |
| Fans | 6 × 15050 dual-ball-bearing fans |
| Max. fan speed | 5,000 RPM |
| Max. fan airflow | 347.2 CFM per fan |
| Reservoir capacity | Approximately 900 mL |
| Pump head (Bykski figure) | 13 m |
| Internal pump power | 4-pin Molex |
| Control | SPD touchscreen with pump and fan PWM adjustment |
| Coolant ports | Rear inlet and outlet, top fill and air-bleed ports |
Which Version Do I Need?
What's in the Box
The unit integrates the pump, reservoir, copper radiator, six cooling fans, and SPD touchscreen.
Installation & Use
For the server loop, prepare GPU water blocks matched to your cards, tubing, matching fittings, and compatible coolant.
FAQ
How much rack space does the cooling unit need?
It uses a 4U mounting position. The chassis measures 452.5 mm deep, 440 mm wide, and 175 mm high. Allow clearance behind it for the hoses.
Is this unit intended for an 8-GPU liquid cooling loop?
Yes. It serves as the cooling unit for that loop. Select water blocks to match each GPU model and PCB.
What does the SPD touchscreen show?
The SPD screen has fields for coolant level, flow, pressure, inlet and outlet coolant temperatures, pump and fan speeds, leak detection, pH, and conductivity.
Where do the supply and return hoses connect?
Confirm the inlet and outlet on your CDU before connecting the hoses. The outlet feeds the server loop, and the inlet takes the return flow.